20.3.1
Identification
SEMOD113212-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
RANGE_XP
-
-
20.3.2
Application
SEMOD52434-4 v5
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGAPC) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits, that is low-low limit, low limit, high limit and
high-high limit. The measure value expander block ( RANGE_XP) has been
introduced to be able to translate the integer output signal from the measuring
functions to 5 binary signals, that is below low-low limit, below low limit, normal,
above high-high limit or above high limit. The output signals can be used as conditions
in the configurable logic.
20.3.3
Setting guidelines
SEMOD113223-4 v1
There are no settable parameters for the measured value expander block function.
20.4
Parameter setting groups
IP1745-1 v1
20.4.1
Application
M12007-6 v9
Six sets of settings are available to optimize IED operation for different power system
conditions. By creating and switching between fine tuned setting sets, either from the
local HMI or configurable binary inputs, results in a highly adaptable IED that can
cope with a variety of power system scenarios.
Different conditions in networks with different voltage levels require highly adaptable
protection and control units to best provide for dependability, security and selectivity
requirements. Protection units operate with a higher degree of availability, especially, if
the setting values of their parameters are continuously optimized according to the
conditions in the power system.
Operational departments can plan for different operating conditions in the primary
equipment. The protection engineer can prepare the necessary optimized and pre-tested
settings in advance for different protection functions. Six different groups of setting
1MRK 505 370-UUS A
Section 20
Basic IED functions
Busbar protection REB670 2.2 ANSI
505
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...