12.2.2.9
ARMode = 1/2/3ph
M12391-127 v8
Single-phase, two-phase or three-phase auto reclosing first shot, followed by 3-phase
auto reclosing shots, if selected. Here, the auto recloser is assumed to be "On" and
"Ready". The circuit breaker is closed and the operation gear ready (operating energy
stored).
START
input (or
STARTHS
) is received and sealed-in. The
READY
output is
reset (set to false).
ACTIVE
output is set.
•
If
TR2P
and
TR3P
inputs are low (i.e. single-phase trip): The timer for single-
phase auto reclosing dead time is started and the
1PT1
output (single-phase
reclosing in progress) is activated. It can be used to suppress pole disagreement
and earth-fault protection trip during the single-phase dead time interval..
•
If
TR2P
input is high and
TR3P
input is low (i.e. two-phase trip): The timer for
two-phase auto reclosing dead time is started and the
2PT1
output (two-phase
reclosing in progress) is activated.
•
If
TR3P
input is high (i.e. three-phase trip): The timer for three-phase auto
reclosing dead time,
t1 3Ph
or
t1 3PhHS
, is started depending on if
START
or
STARTHS
input has been activated and
3PT1
output (three-phase reclosing shot 1
in progress) is set..
While any of the auto reclosing dead time timers are running, the
INPROGR
output is
activated. When the dead time runs out, the respective internal signal is transmitted to
the output module for further checks and to issue a breaker closing command.
When a circuit breaker closing command is issued, the prepare three-pole output trip is
set. When issuing a circuit breaker closing command the
tReclaim
timer is started. If no
tripping takes place during that time, the auto recloser resets to the “Ready” state and
the
ACTIVE
output resets. If the first reclosing shot fails, a three-phase trip will be
initiated and three-phase reclosing can follow, if selected.
12.2.2.10
ARMode = 1/2ph, 1-phase or 2-phase reclosing in the first shot
M12391-136 v5
At single-pole or two-pole tripping, the operation is as in the example described above,
program mode
1/2/3ph
. If the first reclosing shot fails, a three-pole trip will be issued
and three-pole auto reclosing can follow, if selected. In the event of a three-pole trip,
TR3P
input high, the auto recloser will be inhibited and no auto reclosing takes place.
12.2.2.11
ARMode = 1ph+1*2ph, 1-phase or 2-phase reclosing in the first shot
M12391-139 v5
At single-pole tripping, the operation is as in the above described example, program
mode
1/2/3ph
. The single-pole auto reclosing attempt can be followed by three-pole
reclosing, if selected. At two-pole trip, a failure of a two-pole auto reclosing attempt
will inhibit the auto recloser. No more shots are attempted. If the first trip is a three-
pole trip, the auto-reclosing will be inhibited. No more shots are attempted. The
1MRK 505 370-UUS A
Section 12
Control
Busbar protection REB670 2.2 ANSI
321
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...