5.8.3.3
Binary outputs
GUID-A8B580BC-1416-4340-8E66-5E91C43D1665 v1
CB close signal
(Close CB)
CB2 close signal
(Close CB2) **)
Overreach switching signal
(ZExtension)
Definitive trip
(Def. Trip)
Prepare trip of all three phases
(Trip 3-Pol)
Block Follower CB
(BlkFlwr)
Delay Follower CB
(DelFlwr)
Block for Follower recloser
(Inhibit Outp)
Reclosure function ready
(AR Ready)
Reclosure function blocked
(AR Blocked)
Reclosure cycle running
(AR in prog.)
1st single-phase reclosure in progress
(First AR 1P)
1st three-phase reclosure in progress
(First AR 3P)
2nd Reclosure in progress
(Second AR)
3rd reclosure in progress
(Third AR)
4th reclosure in progress
(Fourth AR)
Remark:
**) 2 denotes the inputs for CB2 in a duplex scheme.
5.8.3.4
Measurements
GUID-FC4B02BD-9787-4B7B-870B-725CAE54A890 v1
•
None
5.8.4
Function settings
GUID-EFD006C2-2320-4D06-BF6F-D1EF2609EFFE v1
Table 87: Autoreclosure function - settings
Text
Unit
Default
Min
Max
Step
ParSet 4..1
P1
(Select)
1. AR Mode
1P3P-1P3P
(Select)
2..4. AR Mode
off
(Select)
t Dead1 1P
s
001.20
0.05
300
0.01
t Dead1 3P
s
000.60
0.05
300
0.01
t Dead1 Ext.
s
001.00
0.05
300
0.01
t Dead2
s
001.20
0.05
300
0.01
t Dead3
s
005.00
0.05
300
0.01
t Dead4
s
060.00
0.05
300
0.01
t Oper
s
000.50
0.05
300
0.01
t Inhibit
s
005.00
0.05
300
0.01
t Close
s
000.25
0.05
300
0.01
t Discrim.1P
s
000.60
0.10
300
0.01
t Discrim.3P
s
000.30
0.10
300
0.01
t Timeout
s
001.00
0.05
300
0.01
Table continues on next page
1MRK 505 406-UEN B
Section 5
Bay protection functions
Bay protection functions REB500
131
Technical manual
© Copyright 2019 ABB. All rights reserved