Item
Description
fff
Miliseconds of the recording (Trigger time)
aaa
Station number (1-999)
nnnnn
Fault number (0-65535)
The name of the file can be changed if the records are transferred manually.
4.5.8
Event list
GUID-A88B62AD-8C4C-4062-B978-1B9837159D2C v1
Protection system events are shown in chronological order. By correspondingly setting the
event filter, just protection events, system events or test events can be viewed separately.
Events with an invalid time tag can be excluded from the display. You can choose between
User-defined and System-defined event texts.
12000092-IEC18000500-1-en.vsdx
IEC18000500 V1 EN-US
Figure 19: Event list
The central unit event list has a maximum length of 1000 records; the bay units 100. In the
event of a supply failure, the events stored in the REB500 central unit remain intact for at least
24 hours.
4.5.8.1
Classification of events
GUID-F18BB97F-5B81-4C06-B85D-97EF1DEA19D3 v1
The REB500 system includes two different event lists, the normal and the extended events.
The HMI view Event List enables the selection of the respective class (see
normal
The normal event list shows mainly protection and system events including
diagnosis events in case of major/minor errors which are relevant for the user. For
normal operation of a REB500 system, it is recommended to use the normal event
list view.
extended The extended event list shows further events for diagnosis and error cause
analysis. The vast majority of minor errors falls into this group. The extended event
list view can be helpful for error diagnosis and support activities.
mixed
The mixed event list shows both, the entries of the normal and the extended view.
Section 4
1MRK 500 132-UEN B
HMI500
28
Distributed busbar protection REB500
Operation manual
© Copyright 2019 ABB. All rights reserved