1MRK 505 353-UEN
Section 2
Overview
Application Manual
11
Bay protection functions REB500
2.3.1.5
General outputs from BP
Table 8
BU_ Output signals from BP
Signal
Description
29405_BP blocked
Signals that the outputs of the bay protection functions are
blocked (either the bay concerned or throughout the system).
29410_BP partial blocked
Signals certain bay protection functions are blocked
(Signal must be set explicitly in the bay protection).
29600 ParaSet_1 active
Signals that parameter set 1 is active (activated via the station
bus or an input signal).
29605 ParaSet_2 active
Signals that parameter set 2 is active (activated via the station
bus or an input signal).
29610 ParaSet_3 active
Signals that parameter set 3 is active (activated via the station
bus or an input signal).
29615 ParaSet_4 active
Signals that parameter set 4 is active (activated via the station
bus or an input signal).
Table 9
CU_ Output signals from BP
Signal
Description
49405_BP blocked
Signals that the outputs of the bay protection functions are
blocked (either individual bays or throughout the system).
49410_BP partial blocked
Signals that certain bay protection output signals in specific
bays or throughout the entire system are blocked (Must be
configured together with the corresponding BU output signal
29410_BP partial blocked).
2.3.2
Bay protection
à
function-specific signals
2.3.2.1
Signal designations of binary inputs and outputs
The signal range of REB500 is expanded for the bay protection functions. The BP
function-specific signal can be identified by a 6 digit signal number
Example:
Signal 211105_DIST_Trip CB L1
Table 10
Signal numbers nomenclature
211105
DIST
Trip CB L1
6 Digit signal number
Protection function
Signal designation