Table 583:
LMBRFLO Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
DrepChNoI_A
1 - 30
Ch
1
1
Recorder Input number recording phase
current, IA
DrepChNoI_B
1 - 30
Ch
1
2
Recorder Input number recording phase
current, IB
DrepChNoI_C
1 - 30
Ch
1
3
Recorder Input number recording phase
current, IC
DrepChNoIN
0 - 30
Ch
1
4
Recorder input number recording residual
current, IN
DrepChNoIP
0 - 30
Ch
1
0
Recorder input number recording 3I0 on
parallel line
DrepChNoV_A
1 - 30
Ch
1
5
Recorder Input number recording phase
voltage, VA
DrepChNoV_B
1 - 30
Ch
1
6
Recorder Input number recording phase
voltage, VB
DrepChNoV_C
1 - 30
Ch
1
7
Recorder Input number recording phase
voltage, VC
15.5.6
Technical data
Table 584:
LMBRFLO technical data
Function
Value or range
Accuracy
Reactive and resistive reach
(0.001-1500.000) Ω/phase
± 2.0% static accuracy
± 2.0% degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Phase selection
According to input signals
-
Maximum number of fault
locations
100
-
15.6
Measured value expander block RANGE_XP
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
RANGE_XP
-
-
1MRK505222-UUS C
Section 15
Monitoring
947
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...