V=-3V0
Ipickup
Operate region
I=3Io
mta line
RCADir
ROADir
en05000252_anis.vsd
IEC05000252-ANIS V1 EN
Figure 288:
I & V directional operating principle for CVGAPC function
where:
RCADir is -75°
ROADir is 50°
The second principle, referred to as "
IcosPhi&V
" in the parameter setting tool, checks
that:
•
that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
•
that the phasor of the measured current is within the operating region (defined by
the I·cos(Φ) straight line and the relay operate angle,
ROADir
parameter setting;
see figure
1MRK505222-UUS C
Section 10
Multipurpose protection
573
Technical reference manual