Table 248:
BRCPTOC (46) Output signals
Name
Type
Description
TRIP
BOOLEAN
Operate signal of the protection logic
PICKUP
BOOLEAN
Pickup signal of the protection logic
7.13.5
Setting parameters
Table 249:
BRCPTOC (46) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disable / Enable
IBase
0 - 99999
A
1
3000
IBase
Pickup_ub
50 - 90
%IM
1
50
Unbalance current operation value in percent
of max current
Pickup_PH
5 - 100
%IB
1
20
Minimum phase current for operation of
pickup_ub> in % of Ibase
tOper
0.000 - 60.000
s
0.001
5.000
Operate time delay
Table 250:
BRCPTOC (46) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
tReset
0.010 - 60.000
s
0.001
0.100
Time delay in reset
7.13.6
Technical data
Table 251:
BRCPTOC (46) technical data
Function
Range or value
Accuracy
Minimum phase current for operation
(5–100)% of
IBase
± 0.1% of I
n
Unbalance current operation
(0–100)% of maximum current
± 0.1% of I
n
Timer
(0.00-6000.00) s
± 0.5% ± 10 ms
1MRK505222-UUS C
Section 7
Current protection
489
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...