en06000653_ansi.vsd
INNonDirPU
UN_PU
OpMODE=INcosPhi
Pickup_N
INCosPhiPU
OpMODE=INVNCosPhi
INVNCosPhiPU
Phi in RCA +- ROA
OpMODE=IN and Phi
DirMode = Forw
Forw
DirMode = Rev
Rev
PUNDIN
TRNDIN
PUVN
TRVN
AND
AND
AND
OR
AND
AND
AND
OR
PUDIRIN
PUFW
PUREV
0 - t
0 - t
0
0
TimeChar = DefTime
TRDIRIN
AND
SN
t
TimeChar = InvTime
AND
ANSI06000653 V1 EN-US
Figure 271: Simplified logical diagram of the sensitive ground fault current protection
8.6.8
Technical data
SEMOD173352-1 v1
SEMOD173350-2 v13
Table 249: SDEPSDE (67N) technical data
Function
Range or value
Accuracy
Trip level for 3I
0
·cos
j
directional residual
overcurrent
(0.25-200.00)% of
lBase
±1.0% of I
n
at I
£
I
n
±1.0% of I at I > I
n
Trip level for 3I0·3V
0
·cos
j
directional residual power
(0.25-200.00)% of
SBase
±1.0% of S
n
at S
£
S
n
±1.0% of S at S > S
n
Trip level for 3I
0
and
j
residual overcurrent
(0.25-200.00)% of
lBase
±1.0% of I
n
at
£
I
n
±1.0% of I at I > I
n
Trip level for non-
directional overcurrent
(1.00-400.00)% of
lBase
±1.0% of I
n
at I
£
I
n
±1.0% of I at I > I
n
Table continues on next page
Section 8
1MRK 502 066-UUS B
Current protection
516
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...