Direction
Element
4 step over current
element
One element for each
step
Harmonic
Restraint
Mode
Selection
earthFaultDirection
harmRestrBlock
enableDir
enableStep1-4
DirectionalMode1-4
Element
enableDir
angleValid
Directional Check
operatingCurrent
SwitchOnToFault
start step 2, 3 and 4
signal to communication scheme
TRSOTF
3V0
3I0
Blocking at parallel
transformers
1
CB
pos
or cmd
Element
3I0
DirModeSel
DirModeSel
INPol
ANSI06000376-2-en.vsdx
I3PDIR
TRIP
ANSI06000376 V2 EN-US
Figure 259: Functional overview of EF4PTOC (51N/67N)
8.4.8
Technical data
IP11455-1 v1
M15223-1 v18
Table 234: EF4PTOC (51N/67N) technical data
Function
Range or value
Accuracy
Trip current, step 1-4
(1-2500)% of IBase
±1.0% of I
n
at I ≤ I
n
±1.0% of I at I > I
n
Reset ratio
> 95% at (10-2500)% of
IBase
-
Relay characteristic angle
(RCA)
(-180 to 180) degrees
±2.0 degrees
Trip current for directional release
(1–100)% of IBase
For RCA ±60 degrees:
±2.5% of I
n
at I ≤ I
n
±2.5% of I at I > I
n
Independent time delay at 0 to 2 x I
set
,
step 1-4
(0.000-60.000) s
±0.2% or ±35 ms whichever is greater
Minimum operate time for inverse curves,
step 1-4
(0.000 - 60.000) s
±0.2% or ±35 ms whichever is greater
Inverse time characteristics, see Table
, Table
and Table
16 curve types
See Table
, Table
and Table
Second harmonic blocking
(5–100)% of fundamental
±2.0% of I
n
Minimum polarizing voltage
(1–100)% of VBase
±0.5% of V
n
Minimum polarizing current
(2-100)% of IBase
±1.0% of I
n
Table continues on next page
Section 8
1MRK 502 066-UUS B
Current protection
490
Technical manual
Summary of Contents for Relion 670 series
Page 1: ... RELION 670 SERIES Generator protection REG670 Version 2 1 ANSI Technical manual ...
Page 2: ......
Page 48: ...42 ...
Page 62: ...56 ...
Page 182: ...176 ...
Page 692: ...686 ...
Page 726: ...720 ...
Page 1014: ...1008 ...
Page 1242: ...1236 ...
Page 1362: ...1356 ...
Page 1386: ...1380 ...
Page 1422: ...1416 ...
Page 1431: ...1425 ...