7.5
Importing SCL files to PCM600
The IED engineering tool must be able to receive a SCD file or an ICD file as
import to receive the engineered communication extensions, for example for the
different IEDs.
7.5.1
Importing SCD files
Procedure to import a SCD file to PCM600:
1. Select the station in the plant structure.
2. Right-click the station and select
Import ...
3. Select the file to be imported from the open standard Windows menu and start
the reading.
4. A
SCL Import Options
window opens, which queries how the file should be
IEC09000631-1-en.vsd
IEC09000631 V1 EN
Figure 59:
IEC 61850: Import SCD file
4.1. Click
Ignore Substation Section
to not import the "SSD-file" part of the
SCD-file.
4.2. Click
Don't import IEDs of unknown type
to protect the existing IEDs in
case the SCD file does not match the original configuration in PCM600.
4.3. Click
Replace unknown ...
can be used when it is known, that the file
includes additional IEDs that are needed. The IED of type “Generic IEC
61850 IED” is used to integrate these kinds of IEDs in the plant structure
etc.
4.4. Click
Ignore PCM Object Type
to update the IED object(s) in PCM600
from the IED type(s) in the SCD file, disregarding if the IED type(s) in
the SCD file matches the IED object(s) in PM600 or not.
4.5. Start
Import
when the file definition has been completed. A progress
window presents the import procedure.
5. Make connections from sending IEDs to receiving function blocks in SMT.
1MRK511240-UEN B
Section 7
IEC 61850 communication engineering
670 series
77
Engineering Manual