![ABB Relion 670 series Engineering Manual Download Page 80](http://html1.mh-extra.com/html/abb/relion-670-series/relion-670-series_engineering-manual_3477086080.webp)
7.3.1
Exporting SCD files
Procedure to export the SCD file from PCM600:
1. Select the station in the plant structure, see
IEC08000415.vsd
Station
IEC08000415 V1 EN
Figure 55:
IEC 61850: Export SCD step 1
2. Right-click the station and select
Export ....
3. Select a location from the open standard Windows menu to store the file and
name it.
4. The
SCL Export Options
window opens, see
IEC09000627-1-en.vsd
IEC09000627 V1 EN
Figure 56:
IEC 61850: SCL Export Options
5. Select
Export Private Sections
and click
Export
to export the private sections
to the SCD file. A progress window shows the ongoing export of the station.
7.3.2
Exporting ICD or CID files
Procedure to select the export type, when the IED is selected in the plant structure:
1. Right-click the IED in the plant structure and select
Export
to open the
Export
window.
2. Select the type of file to export from the
Save as type
drop down list.
Section 7
1MRK511240-UEN B
IEC 61850 communication engineering
74
670 series
Engineering Manual