For more details please refer to the IEC 61850 standards. In the following
description it is assumed that PCM600 together with IET600 is used as system
configuration tool.
A short form of a typical sequence is shown in
when a complete station
is exported as a SCD file.
1. Export SCL files from PCM600. In the scenario in
it is a SCD file.
Other SCL file types are possible to export.
2. Configure horizontal and vertical communication in the IET600 station
configuration tool.
3. Import SCL files to PCM600 project. In the scenario in
updated SCD file.
SCD file
do IED engineering
export SCD file
PCM600 (1)
create project
import SCD file
configure data sets
configure Report CBs
configure GOOSE CBs
export SCD file
IET600 (2)
import SCD file
link GOOSE input data
Write to IED
PCM600 (3)
SCD file
IED 1
IED n
IED 2
IED n-1
IEC11000264.vsd
IEC11000264 V1 EN
Figure 54:
IEC 61850: Signal engineering procedure flow
7.3
Exporting SCL files from PCM600
A pre-condition is that all IEDs in the project must be engineered in PCM600. The
hardware interface, for example the communication port, has to be selected and
configured. The used interface addresses have to be set according to protocol and
project definitions. The station communication port has to be activated in the IED,
that is to set the IEC61850-8-1
Operation
setting to
On
.
1MRK511240-UEN B
Section 7
IEC 61850 communication engineering
670 series
73
Engineering Manual