For time synchronization of line differential protection RED670 with diff communication in
GPS-mode, a GPS-based time synchronization is needed. This can be optical IRIG-B with 1344
from an external GPS-clock or an internal GPS-receiver.
For IEDs using IEC 61850-9-2LE in "mixed mode" a time synchronization from an external clock
is recommended to the IED and all connected merging units. The time synchronization from
the clock to the IED can be either optical PPS or IRIG-B. For IED's using IEC 61850-9-2LE from
one single MU as analog data source, the MU and IED still needs to be synchronized to each
other. This could be done by letting the MU supply a PPS signal to the IED.
Out of these, LON and SPA contains two types of synchronization messages:
•
Coarse time messages are sent every minute and contain complete date and time, that is
year, month, day, hour, minute, second and millisecond.
•
Fine time messages are sent every second and comprise only seconds and milliseconds.
The selection of the time source is done via the corresponding setting.
It is possible to set a backup time-source for GPS signal, for instance SNTP. In this case, when
the GPS signal quality is bad, the IED will automatically choose SNTP as the time-source. At a
given point in time, only one time-source will be used.
22.13.2
Setting guidelines
IP15089-1 v3
All the parameters related to time are divided into two categories: System time and
Synchronization.
22.13.2.1
System time
M11348-119 v4
The time is set with years, month, day, hour, minute, second and millisecond.
22.13.2.2
Synchronization
M11348-143 v4
The setting parameters for the real-time clock with external time synchronization are set via
local HMI or PCM600. The path for Time Synchronization parameters on local HMI is Main
menu/Configuration/Time/Synchronization. The parameters are categorized as Time
Synchronization (TIMESYNCHGEN) and IRIG-B settings (IRIG-B:1) in case that IRIG-B is used as
the external time synchronization source.
TimeSynch
M11348-167 v18
When the source of the time synchronization is selected on the local HMI, the parameter is
called
TimeSynch. The time synchronization source can also be set from PCM600. The setting
alternatives are:
FineSyncSource can have the following values:
•
Off
•
SPA
•
LON
•
BIN (Binary Minute Pulse)
•
GPS
•
GPS+SPA
•
GPS+LON
•
GPS+BIN
•
SNTP
•
GPS+SNTP
Section 22
1MRK 505 343-UEN B
Basic IED functions
730
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...