16.8
Boolean 16 to Integer conversion B16I
SEMOD175715-1 v1
16.8.1
Identification
SEMOD175721-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion
B16I
-
-
16.8.2
Application
SEMOD175832-4 v4
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical)
signals into an integer. It can be used – for example, to connect logical output signals from a
function (like distance protection) to integer inputs from another function (like line differential
protection). B16I does not have a logical node mapping.
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16
binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum
of all the values on the activated INx will be available on the output OUT as a sum of the values
of all the inputs INx that are activated. OUT is an integer. When all INx where 1≤x≤16 are
activated that is = Boolean 1 it corresponds to that integer 65535 is available on the output
OUT. B16I function is designed for receiving up to 16 booleans input locally. If the BLOCK input
is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block B16I.
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
Section 16
1MRK 505 343-UEN B
Logic
642
Application manual
Summary of Contents for Relion 670 series
Page 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Page 2: ......
Page 40: ...34...
Page 64: ...58...
Page 150: ...144...
Page 406: ...400...
Page 472: ...466...
Page 494: ...488...
Page 512: ...506...
Page 524: ...518...
Page 604: ...598...
Page 686: ...680...
Page 718: ...712...
Page 722: ...716...
Page 758: ...752...
Page 759: ...753...