The outer boundary of oscillation detection characteristic in forward direction
RLdOutFw
should be set with certain safety margin K
L
compared to the minimum expected load
resistance R
Lmin
. When the exact value of the minimum load resistance is not known, the
following approximations may be considered for lines with rated voltage 400 kV:
•
K
L
= 0.9 for lines longer than 150 km
•
K
L
= 0.85 for lines between 80 and 150 km
•
K
L
= 0.8 for lines shorter than 80 km
Multiply the required resistance for the same safety factor K
L
with the ratio between actual
voltage and 400kV when the rated voltage of the line under consideration is higher than
Section 7
1MRK 505 343-UEN B
Impedance protection
368
Application manual