This is the case when
VBase
is equal to the transformer rated voltages.
For other values, the percentage settings need to be adjusted
accordingly.
When the overexcitation is equal to the set value of
Pickup2
, tripping is obtained after
a time equal to the setting of t6. A suitable setting would be
Pickup2
= 140% and t6 =
4 s.
The interval between
Pickup2
and
Pickup1
is automatically divided up in five equal
steps, and the time delays t2 to t5 will be allocated to these values of overexcitation. In
this example, each step will be (140-105) /5 = 7%. The setting of time delays t1 to t6
are listed in table
.
Table 47:
Settings
V/f op (%)
Timer
Time set (s)
105
t1
7200 (max)
112
t2
600
119
t3
60
126
t4
20
133
t5
8
140
t6
4
Information on the cooling time constant T
cool
should be retrieved from the power
transformer manufacturer.
1MRK 502 071-UUS A
Section 10
Voltage protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
459
Application manual