Section 1
Operate
conditionally
UnrestrainedLimit
Section 2
Section 3
Restrain
Operate
unconditionally
5
4
3
2
1
0
0
1
2
3
4
5
IdMin
EndSection1
EndSection2
restrain current
[ times IBase ]
operate current
[ times IBase ]
SlopeSection2
SlopeSection3
en05000187-2.vsd
IEC05000187 V2 EN-US
Figure 52:
Representation of the restrained, and the unrestrained operate
characteristics
100%
Ioperate
slope
Irestrain
D
= D
×
EQUATION1246 V1 EN-US
(Equation 13)
and where the restrained characteristic is defined by the settings:
1.
IdMin
2.
EndSection1
3.
EndSection2
4.
SlopeSection2
5.
SlopeSection3
1MRK 502 071-UUS A
Section 7
Differential protection
Generator protection REG670 2.2 ANSI and Injection equipment REX060, REX061, REX062
137
Application manual