17.4.8.4
Signals
GUID-2DC54788-86AF-4B4B-8E57-A89E30F0C433 v1
Except for the BLOCK input, the rest of the inputs of this GOOSE
function block are used for GOOSE connections. These
connections are visible and possible to make only if Easy GOOSE
engineering is enabled. For instructions on how to enable Easy
GOOSE engineering in PCM600, refer to the
Engineering Manual
.
PID-6829-INPUTSIGNALS v3
Table 492:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
SRCINTOUT
INTEGER
0
Source to integer output
PID-6829-OUTPUTSIGNALS v3
Table 493:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
17.4.8.5
Settings
PID-6829-SETTINGS v3
Table 494:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
17.4.8.6
Operation principle
GUID-5BBDF772-3B3E-4F7C-ABE9-18CE3C1A2E2D v4
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not
happen.
The TEST output will go HIGH if the sending IED is in test mode.
Section 17
1MRK 506 382-UEN A
Station communication
682
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...