If the fault inception function has detected a system fault, a block signal CS will be
issued and sent to remote end in order to block the overreaching zones. Different
criteria has to be fulfilled for sending the CS signal:
1. The breaker has to be in closed condition, that is, the input signal CBOPEN is
deactivated.
2. A fault inception should have been detected while the carrier send signal is not
blocked, that is, the input signal BLKCS is not activated.
If it is later detected that it was an internal fault that made the function issue the CS
signal, the function will issue a CHSTOP signal to unblock the remote end.
The received signal, which is connected to the CR input, is not used to accelerate
the release of the overreaching zone to clear the fault instantaneously. The
overreaching zone to be accelerated is connected to the input CACC, see
.
In case of external faults, the blocking signal (CR) must be received before the
settable timer
tCoord
elapses, to prevent a false trip, see
The function can be totally blocked by activating the input BLOCK, block of trip
by activating the input BLKTR, block of carrier send by activating the input
BLKCS.
CACC
CR
tCoord
TRIP
AND
t
en05000512.vsd
IEC05000512 V1 EN-US
Figure 218:
Basic logic for trip signal in delta blocking scheme
Channels for communication in each direction must be available.
12.1.6.3
Permissive underreaching scheme
M13893-13 v6
In a permissive underreaching scheme, a forward directed underreaching
measuring element (normally zone1) sends a permissive signal CS to the remote
end if a fault is detected.in forward direction. The received signal CR is used to
allow an overreaching zone to trip after the
tCoord
timer has elapsed. The
tCoord
in permissive underreaching schemes is normally set to zero.
The logic for trip signal in permissive scheme is shown in figure
CACC
CR
tCoord
TRIP
AND
t
en05000513.vsd
IEC05000513 V1 EN-US
Figure 219:
Logic for trip signal in permissive scheme
1MRK 506 382-UEN A
Section 12
Scheme communication
Line distance protection REL650 2.2 IEC
437
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...