control function reflecting the switchyard configuration. The total number used
depends on the switchyard configuration. These types are:
•
Bay control QCBAY
•
Switch controller SCSWI
•
Circuit breaker SXCBR
Another function block type for supervision and control is the XLNPROXY. It is
used for interfacing a switch with its primary representation in a breaker IED.
XLNPROXY facilitates a common interface with the SXCBR function towards the
SCSWI function, especially for command response and error handling.
The functions Local Remote (LOCREM) and Local Remote Control
(LOCREMCTRL), to handle the local/remote switch, also belong to the apparatus
control function.
The principles of operation, function blocks, input and output signals and setting
parameters for all these functions are described below.
11.4.3
Error handling
GUID-6C31D291-74E8-46A3-8FC2-D3959C2458A5 v6
Depending on the error that occurs during the command sequence the error signal
will be set with a value. Table
describes the cause values given on local HMI.
The translation to AddCause values specified in IEC 61850-8-1 is shown in Table
. For IEC 61850-8-1 edition 2 only addcauses defined in the standard are used,
for edition 1 also a number of vendor specific causes are used. The values are
available in the command response to commands from IE C61850-8-1 clients. An
output L_CAUSE on the function block for Switch controller (SCSWI) and Circuit
breaker (SXCBR) indicates the value of the cause during the latest command if the
function specific command evaluation has been started. The causes that are not
always reflected on the output L_CAUSE, with description of the typical reason
are listed in table
.
Table 208:
Values for "cause" signal
Cause
number
Name
Description
Supported
0
None
Control action successfully executed
X
1
Not-supported
Given for Cancel request with Direct Control in Ready
state
X
2
Blocked-by-
switching-hierarchy
Not successful since one of the downstream Loc
switches like in CSWI has the value TRUE
X
3
Select-failed
Cancelled due to an unsuccessful selection (select
service)
X
4
Invalid-position
Control action is aborted due to invalid switch position
(Pos in XCBR)
X
5
Position-reached
Switch is already in the intended position (Pos in
XCBR)
X
6
Parameter-change-
in-execution
Control action is blocked due to running parameter
change
X
Table continues on next page
Section 11
1MRK 506 382-UEN A
Control
382
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...