Table 125:
Dependencies between parameters RetripMode and FunctionMode
RetripMode
FunctionMode
Description
Retrip Off
N/A
The re-trip function is not
activated.
CB Pos Check
Current
The re-trip will follow the
function mode.
Contact
Current/Contact
No CBPos Check
Current
The re-trip is done
unconditionally.
Contact
Current/Contact
The start signal can be an internal or external protection trip signal. This signal will
start the back-up trip timer. The function detects the successful breaker opening,
either by detection of low current through RMS evaluation and a special adapted
current algorithm or by open contact indication. The special algorithm enables a
very fast detection of successful breaker opening, that is, fast resetting of the
current measurement. If the current and/or contact detection has not detected
breaker opening before the back-up timer has run its time a back-up trip is initiated.
Further the following possibilities are available:
•
The minimum length of the re-trip pulse, the back-up trip pulse and the back-
up trip pulse 2 are settable. The re-trip pulse, the back-up trip pulse and the
back-up trip pulse 2 will however sustain as long as there is an indication of
closed breaker.
•
In the current detection it is possible to use three different options:
1 out of 3
where it is sufficient to detect failure to open (high current) in one pole,
1 out
of 4
where it is sufficient to detect failure to open (high current) in one pole or
high residual current and
2 out of 4
where at least two current (phase current
and/or residual current) shall be high for breaker failure detection.
•
The current detection level for the residual current can be set different from the
setting of phase current detection.
•
It is possible to have different back-up time delays for single-phase faults and
for multi-phase faults.
•
The back-up trip can be made without current check. It is possible to have this
option activated for small load currents only.
•
It is possible to have instantaneous back-up trip function if a signal is high if
the circuit breaker is incapable to clear faults, for example at low gas pressure.
Section 7
1MRK 506 382-UEN A
Current protection
242
Line distance protection REL650 2.2 IEC
Technical manual
Summary of Contents for RELION 650 SERIES
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Page 2: ......
Page 46: ...40 ...
Page 56: ...50 ...
Page 164: ...158 ...
Page 264: ...258 ...
Page 304: ...298 ...
Page 320: ...314 ...
Page 338: ...332 ...
Page 438: ...432 ...
Page 468: ...462 ...
Page 534: ...528 ...
Page 646: ...640 ...
Page 660: ...654 ...
Page 676: ...670 ...
Page 800: ...794 ...
Page 836: ...830 ...
Page 890: ...884 ...
Page 894: ...888 ...
Page 940: ...934 ...
Page 941: ...935 ...