16.1.6.3
Non-directional instantaneous and definitive time, phase and residual
overcurrent protection
M11622-3 v4
The CTs must have a rated equivalent secondary e.m.f. E
al
that is larger than or equal to the
required secondary e.m.f. E
alreq
below:
s n
R
a l
a lre q
CT
L
2
pn
n
op
I
S
E
E
1.5 I
R
R
I
I
³
=
×
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1678 V1 EN-US
(Equation 33)
where:
I
op
The primary operate value (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
n
The nominal current of the protection IED (A)
R
CT
The secondary resistance of the CT (
W
)
R
L
The resistance of the secondary cable and additional load (
W
). The loop resistance containing the phase
and neutral wires, must be used for faults in solidly grounded systems. The resistance of a single
secondary wire should be used for faults in high impedance grounded systems.
S
R
The burden of an IED current input channel (VA). S
R
=0.010 VA/channel for I
r
=1 A and S
R
=0.250 VA/channel
for I
r
=5 A
16.1.6.4
Non-directional inverse time delayed phase and residual overcurrent
protection
M11339-3 v4
The requirement according to Equation
does not need to be fulfilled if the high
set instantaneous or definitive time stage is used. In this case Equation is the only necessary
requirement.
If the inverse time delayed function is the only used overcurrent protection function the CTs must
have a rated equivalent secondary e.m.f. E
al
that is larger than or equal to the required secondary
e.m.f. E
alreq
below:
s n
R
a l
a lre q
CT
L
2
pn
n
op
I
S
E
E
20 I
R
R
I
I
³
=
×
×
+
+
æ
ö
×
ç
÷
è
ø
EQUATION1679 V1 EN-US
(Equation 34)
where
I
op
The primary current set value of the inverse time function (A)
I
pn
The rated primary CT current (A)
I
sn
The rated secondary CT current (A)
I
n
The nominal current of the protection IED (A)
Table continues on next page
1MRK 505 287-UUS B
Section 16
Requirements
Busbar protection REB650
243
Application manual
© Copyright 2013 ABB. All rights reserved
Summary of Contents for RELION 650 SERIES
Page 1: ...Relion 650 SERIES Busbar protection REB650 Version 1 3 ANSI Application manual...
Page 2: ......
Page 22: ...16...
Page 34: ...28...
Page 56: ...50...
Page 64: ...58...
Page 76: ...70...
Page 120: ...114...
Page 184: ...178...
Page 216: ...210...
Page 220: ...214...
Page 254: ...248...
Page 261: ...255...