Table 16:
Warning indications
Warning indication
Additional information
Warning
IEC 61850 Error
IEC 61850 has not succeeded
in some actions such as
reading the configuration file,
startup etc.
Warning
GOOSE Error
One or more access point is
not able to run GOOSE due to
GOOSE being deactivated on
the access point, or the
access point being
deactivated or failing.
Warning
DNP3 Error
Error in DNP3
communication.
8.2.3
Additional indications
GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3
The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status
data is found under the IED status and in the internal event list.
Table 17:
Additional indications
Warning indication
Additional information
Time Synch Error
Source of the time synchronization is lost or time
system has made a time reset.
Settings Changed
Settings have been changed.
Setting Groups Changed
Setting group has been changed.
8.3
Correction procedures
8.3.1
Creating user accounts and setting and changing
passwords
GUID-D3FA85BA-1E36-4F8B-BD71-85C7AC46A0B4 v2
If Central Account Management is disabled in the IED, user account creation,
initial password setting and password changing is done using PCM600.
If Central Account Management is enabled in the IED, user account creation and
initial password setting is done using the SDM600 server. Individual users can then
change their passwords via PCM600 or the LHMI.
For more information, see PCM600 documentation or the Cyber
security deployment guidelines.
Section 8
1MRK 500 128-UEN B
Troubleshooting
80
650 series 2.2 IEC
Operation manual