8.2.5
Settings
Table 75:
OV2PTOV Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OperationStep1
Off
On
-
-
On
Enable execution of step 1
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
-
-
Definite time
Selection of time delay curve type for step
1
OpMode1
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 1
U1>
1 - 200
%UB
1
120
Voltage start value (DT & IDMT) in % of
UBase for step 1
t1
0.00 - 6000.00
s
0.01
5.00
Definite time delay of step 1
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves
for step 1
k1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay
for step 1
OperationStep2
Off
On
-
-
On
Enable execution of step 2
OpMode2
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 2
U2>
1 - 200
%UB
1
150
Voltage start value (DT & IDMT) in % of
UBase for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definite time delay of step 2
Table 76:
OV2PTOV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
-
-
PhN DFT
Group selector for connection type
8.2.6
Monitored data
Table 77:
OV2PTOV Monitored data
Name
Type
Values (Range)
Unit
Description
UL1
REAL
-
kV
Voltage in phase L1
UL2
REAL
-
kV
Voltage in phase L2
UL3
REAL
-
kV
Voltage in phase L3
1MRK 505 288-UEN A
Section 8
Voltage protection
135
Technical manual
Summary of Contents for Relion 650 Series REB650
Page 1: ...Relion 650 series Busbar protection REB650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 44: ...38 ...
Page 58: ...52 ...
Page 80: ...74 ...
Page 84: ...78 ...
Page 152: ...146 ...
Page 278: ...272 ...
Page 316: ...310 ...
Page 432: ...426 ...
Page 504: ...498 ...
Page 518: ...512 ...
Page 566: ...560 ...
Page 567: ...561 ...