Description of the substation part including the used logical nodes
•
Description of the IEDs with their logical nodes
•
Description of the communication network
•
Description of the engineering process
For more details please refer to the IEC 61850 standards. In the following description it
is assumed that PCM600 together with CCT600 is used as system configuration tool.
A short form of a typical sequence is shown in
when a complete station is
exported as a SCD file.
1. Export SCL files from PCM600. In the scenario in
it is a SCD file.
Other SCL file types are possible to export.
2. Configure horizontal and vertical communication in the station configuration tool,
for example CCT600.
3. Import SCL files to PCM600 project. In the scenario in
SCD file.
IEC08000413.vsd
SCD file
è
do IED engineering
è
export SCD file
PCM600 (1)
è
create project
è
import SCD file
è
configure data sets
è
configure Report CBs
è
configure GOOSE CBs
è
export SCD file
CCT600 (2)
è
import SCD file
è
link GOOSE input data
è
Write to IED
PCM600 (3)
SCD file
IED 1
IED n
IED 2
IED n-1
IEC08000413 V1 EN
Figure 62:
IEC 61850: Signal engineering procedure flow
1MRK 511 245-UUS -
Section 7
IEC 61850 communication engineering
650 series ANSI
97
Engineering Manual