Figure 34:
Configuration for using an instance in task time group 1 as DFT
reference
Assume instance SMAI_20_7:1 in task time group 1 has been selected in the
configuration to control the frequency tracking (For the SMAI_20_x task time
groups). Observe that the selected reference instance must be a voltage type.
For task time group 1 this gives the following settings:
SMAI_20_7:1:
DFTRefExtOut
=
DFTRefGrp7
to route SMAI_20_7:1 reference to
the SPFCOUT output,
DFTReference
=
DFTRefGrp7
for SMAI_20_7:1 to use
SMAI_20_7:1 as reference.
SMAI_20_2:1 - SMAI_20_12:1
DFTReference
=
DFTRefGrp7
for SMAI_20_2:1 -
SMAI_20_12:1 to use SMAI_20_7:1 as reference.
For task time group 2 this gives the following settings:
SMAI_20_1:2 - SMAI_20_12:2
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input as reference (SMAI_20_7:1)
3.9
Measured value expander block MVEXP
3.9.1
Function block
MVEXP
RANGE*
HIGHHIGH
HIGH
NORMAL
LOW
LOWLOW
IEC09000215-1-en.vsd
IEC09000215 V1 EN
Figure 35:
Function block
3.9.2
Functionality
The current and voltage measurements functions (CMMXU, RESCMMXU,
RESVMMXU, VPHMMXU, VPPMMXU and PWRMMXU), current and voltage
sequence measurement functions (CSMSQI and VSMSQI) and IEC 61850 generic
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
65
Technical Manual