Table 62: 2RTD/1mA monitored data
Name
Type
Values (Range)
Unit
Description
AI_DB1
FLOAT32
-10000.0...10000.
0
mA input, Con-
nectors 1-2, re-
ported value
AI_RANGE1
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
mA input, Con-
nectors 1-2,
range
AI_DB2
FLOAT32
-10000.0...10000.
0
RTD input, Con-
nectors 3-5, re-
ported value
AI_RANGE2
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Con-
nectors 3-5,
range
AI_DB3
FLOAT32
-10000.0...10000.
0
RTD input, Con-
nectors 6-8, re-
ported value
AI_RANGE3
Enum
0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Con-
nectors 6-8,
range
3.14
SMV function blocks
SMV function blocks are used in the process bus applications with the sending of
the sampled values of analog currents and voltages and with the receiving of the
sampled values of voltages.
3.14.1
IEC 61850-9-2 LE sampled values sending SMVSENDER
3.14.1.1
Functionality
The SMVSENDER function block is used for activating the SMV sending
functionality. It adds/removes the sampled value control block and the related data
set into/from the sending device's configuration. It has no input or output signals.