![ABB Relion 620 Series Manual Download Page 18](http://html1.mh-extra.com/html/abb/relion-620-series/relion-620-series_manual_3414585018.webp)
Section 2
1MAC302441-MB A
IEC 60870-5-101/104 data mappings
12
RER620
Point List Manual
2.2
Point list for RER620 Ver. 1.0
Table 2:
Analog values
No events 61850 Path
IOA
Disabled
Description
Multiplier Interrogation
CMMXU1.A.phsA.cVal.mag.f
8000
"IA,IB,IC:phase A amplitude"
Yes
CMMXU1.A.phsA.instCVal.ang.f
8001
"IA,IB,IC:phase A angle"
Yes
CMMXU1.A.phsB.cVal.mag.f
8003
"IA,IB,IC:phase B amplitude"
Yes
CMMXU1.A.phsB.instCVal.ang.f
8004
"IA,IB,IC:phase B angle"
Yes
CMMXU1.A.phsC.cVal.mag.f
8006
"IA,IB,IC:phase C amplitude"
Yes
CMMXU1.A.phsC.instCVal.ang.f
8007
"IA,IB,IC:phase C angle"
Yes
CSMSQI1.SeqA.c1.cVal.mag.f
8012
"I1,I2,I0:amplitude"
Yes
CSMSQI1.SeqA.c1.instCVal.ang.f
8013
"I1,I2,I0:angle"
Yes
CSMSQI1.SeqA.c2.cVal.mag.f
8015
"I1,I2,I0:amplitude"
Yes
CSMSQI1.SeqA.c2.instCVal.ang.f
8016
"I1,I2,I0:angle"
Yes
CSMSQI1.SeqA.c3.cVal.mag.f
8018
"I1,I2,I0:amplitude"
Yes
CSMSQI1.SeqA.c3.instCVal.ang.f
8019
"I1,I2,I0:angle"
Yes
FLTMSTA1.OpCnt.stVal
8024
FLTMSTA1:OpCnt status
Yes
FMMXU1.Hz.mag.f
8025
f:Hz magnitude
Yes
FRPTRC1.StrDur.mag.f
8026
Freq1:StrDur magnitude
Yes
FRPTRC2.StrDur.mag.f
8027
Freq2:StrDur magnitude
Yes
PEMMXU1.TotPF.mag.f
8032
"P,E:TotPF magnitude"
Yes
PEMMXU1.TotW.mag.f
8033
"P,E:TotW magnitude"
Yes
PEMMXU1.TotVA.mag.f
8034
"P,E:TotVA magnitude"
Yes
PEMMXU1.TotVAr.mag.f
8035
"P,E:TotVAr magnitude"
Yes
RESCMMXU1.A.res.cVal.mag.f
8036
IG:amplitude
Yes
RESCMMXU1.A.res.instCVal.ang.f
8037
IG:angle
Yes
SDARREC1.OpCnt1.stVal
8041
79:OpCnt1 status
Yes
SDARREC1.OpCnt2.stVal
8042
79:OpCnt2 status
Yes
SDARREC1.OpCnt3.stVal
8043
79:OpCnt3 status
Yes
SDARREC1.OpCnt4.stVal
8044
79:OpCnt4 status
Yes
SDARREC1.OpCnt5.stVal
8045
79:OpCnt5 status
Yes
VMMXU1.PhV.phsA.cVal.ang.f
8046
"VA,VB,VC:phase A angle"
Yes
VMMXU1.PhV.phsA.cVal.mag.f
8047
"VA,VB,VC:phase A amplitude"
Yes
VMMXU1.PhV.phsB.cVal.ang.f
8048
"VA,VB,VC:phase B angle"
Yes
VMMXU1.PhV.phsB.cVal.mag.f
8049
"VA,VB,VC:phase B amplitude"
Yes
VMMXU1.PhV.phsC.cVal.ang.f
8050
"VA,VB,VC:phase C angle"
Yes
VMMXU1.PhV.phsC.cVal.mag.f
8051
"VA,VB,VC:phase C amplitude"
Yes
VMMXU1.PPV.phsAB.cVal.mag.f
8052
"VA,VB,VC:phase AB amplitude"
Yes
VMMXU1.PPV.phsAB.instCVal.ang.f
8053
"VA,VB,VC:phase AB angle"
Yes
VMMXU1.PPV.phsBC.cVal.mag.f
8055
"VA,VB,VC:phase BC amplitude"
Yes
VMMXU1.PPV.phsBC.instCVal.ang.f
8056
"VA,VB,VC:phase BC angle"
Yes
Summary of Contents for Relion 620 Series
Page 2: ......
Page 8: ...Table of contents 1MAC302441 MB A 2 RER620 Point List Manual...
Page 16: ...Section 1 1MAC302441 MB A Introduction 10 RER620 Point List Manual...
Page 44: ...Section 2 1MAC302441 MB A IEC 60870 5 101 104 data mappings 38 RER620 Point List Manual...
Page 58: ...Section 4 1MAC302441 MB A Glossary 52 RER620 Point List Manual...
Page 59: ......