4.4.2.7
Settings
Table 489:
46PD Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Pickup value
10...100
%
1
10
Pickup value
Trip delay time
100...30000
ms
1
100
Trip delay time
Table 490:
46PD Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Table 491:
46PD Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Min phase current
0.05...0.30
xIn
0.01
0.10
Minimum phase current
4.4.2.8
Monitored data
Table 492:
46PD Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
RATIO_I2_I1
FLOAT32
0.00...999.99
%
Measured current ratio I2 / I1
46PD
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
4.4.2.9
Technical data
Table 493:
46PD Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
±2% of the set value
Pickup time
<70 ms
Reset time
Typically 40 ms
Table continues on next page
Section 4
1MAC059074-MB A
Protection functions
598
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......