4.4.1.9
Technical data
Table 485:
46 Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±1.5% of the set value or ±0.002 × I
n
Pickup time
1)2)
Minimum
Typical
Maximum
I
Fault
= 2 × set
Pickup
value
I
Fault
= 10 × set
Pickup
value
23 ms
15 ms
26 ms
18 ms
28 ms
20 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Negative sequence current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Maximum
Pickup value = 2.5 × I
n
,
Pickup value multiples in range of 1.5...20
4.4.1.10
Technical revision history
Table 486:
46 Technical revision history
Technical revision
Change
B
Minimum and default values changed to 40 ms for
the
Trip delay time setting
C
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting
D
Internal improvement
E
Internal Improvements
4.4.2
Phase discontinuity protection 46PD
4.4.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase discontinuity protection
PDNSPTOC
I2/I1>
46PD
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
593
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......