Table 258:
67/51P Technical revision history
Technical revision
Change
B
Added a new input
NON_DIR
C
Step value changed from 0.05 to 0.01 for the
Time
multiplier setting.
D
Monitored data VMEM_USED indicating voltage
memory use.
E
Internal improvement.
4.1.3
Three-phase voltage-dependent overcurrent protection 51V
4.1.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Three-phase voltage-dependent
overcurrent protection
PHPVOC
3I(U)>
51V
4.1.3.2
Function block
TRIP
PICKUP
I_B
51V
I_C
V_BC
V_AB
V_CA
I_A
BLOCK
ENA_MULT
ENA_U_MULT
GUID-6290E1B0-0380-40DD-A5AF-60D789C30DF2 V1 EN
Figure 126:
Function block
4.1.3.3
Functionality
The three-phase voltage-dependent overcurrent protection function 51V is used for
single-phase, two-phase or three-phase voltage-dependent time overcurrent protection of
generators against overcurrent and short circuit conditions.
The function picks up when the input phase current exceeds a limit which is dynamically
calculated based on the measured terminal voltages. The operating characteristics can be
selected to be either inverse definite minimum time IDMT or definite time DT.
Section 4
1MAC059074-MB A
Protection functions
258
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......