4.1.1.11
Technical data
Table 231:
51P, 50P, 50P-3 Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
current: f
n
±2 Hz
51P
±1.5% of the set value or ±0.002 × I
n
50P
and
50P-3
±1.5% of set value or ±0.002 × I
n
(at currents in the range of 0.1…10 × I
n
)
±5.0% of the set value
(at currents in the range of 10…40 × I
n
)
Pickup time
1)2)
Minimum
Typical
Maximum
50P-3:
I
Fault
= 2 × set
Pickup
value
I
Fault
= 10 × set
Pickup
value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
50P and 51P:
I
Fault
= 2 × set
Pickup
value
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Measurement mode = default (depends on stage), current before fault = 0.0 × I
n
, f
n
= 50 Hz, fault current in
one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum
Pickup value = 2.5 × I
n
,
Pickup value multiples in range of 1.5...20
Section 4
1MAC059074-MB A
Protection functions
230
615 series ANSI
Technical Manual
Summary of Contents for Relion 615 series
Page 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Page 2: ......
Page 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Page 40: ...34 ...
Page 64: ...58 ...
Page 216: ...210 ...
Page 884: ...878 ...
Page 1038: ...1032 ...
Page 1136: ...1130 ...
Page 1172: ...1166 ...
Page 1180: ...1174 ...
Page 1186: ...1180 ...
Page 1192: ...1186 ...
Page 1193: ...1187 ...
Page 1194: ......
Page 1195: ......