Table 227:
50P-3 Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
4.1.1.10
Monitored data
Table 228:
51P Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
51P
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 229:
50P Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50P
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
Table 230:
50P-3 Monitored data
Name
Type
Values (Range)
Unit
Description
PICKUP_DUR
FLOAT32
0.00...100.00
%
Ratio of pickup time / trip time
50P-3
Enum
1=Enabled
2=blocked
3=test
4=test/blocked
5=Disabled
Status
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
229
Technical Manual