A071150 V3 EN
Figure 86:
Active setting group
2.
Select the setting group with
or
.
3.
Press
to confirm the selection or
to cancel.
A071152 V3 EN
Figure 87:
Selecting the active setting group
4.
Commit the settings.
Remember to document the changes you make.
8.5.3.2
IED parametrization
IED parameters are set via the LHMI, WHMI or PCM600.
Setting parameters need to be calculated according to the electrical network
conditions and the electrical characteristics of the protected equipment. The IED's
settings need to be verified before the IED is connected to a system.
1MRS756708 C
Section 8
Commissioning
615 series
115
Operation Manual