Table 31. Residual overvoltage protection (ROVPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 2 × set
Start value
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Residual voltage before fault = 0.0 × U
n
, f
n
= 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2)
Includes the delay of the signal output contact
Table 32. Residual overvoltage protection (ROVPTOV) main settings
Parameter
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 × U
n
0.001
Operate delay time
ROVPTOV
40...300000 ms
1
Table 33. Three-phase undervoltage protection (PHPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 0.9 × set
Start value
62 ms
66 ms
70 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Start value = 1.0 × U
n
, Voltage before fault = 1.1 × U
n
, f
n
= 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2)
Includes the delay of the signal output contact
3)
Minimum
Start value = 0.50, Start value multiples in range of 0.90...0.20
Voltage Protection and Control
1MRS757058 K
REU615
Product version: 5.0 FP1
ABB
29