Alarm 6
TPGAPC7_IN2
SELGAPC4_IN_18
OSWGAPC16
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
TCSSCBR1_ALARM
TRPPTRC1_CL_LKOUT
TRPPTRC2_CL_LKOUT
HZCCASPVC1_ALARM
RDRE_TRIGGERED
CCBRBRF1_TRBU
CCBRBRF1_TRRET
SELGAPC1_OUT_6
HZCCCSPVC1_ALARM
HZCCBSPVC1_ALARM
External Trip
GUID-FD9EDBEE-F36B-4128-8D8C-3BFCB7E6967F V2 EN
Figure 50:
OSWGAPC16
3.4.4.4
GOOSE
In the configuration, there are 20 GOOSERCV_BIN functions. Each
GOOSERVC_BIN function can be connected to one received binary GOOSE signal.
The signal connection can be configured in PCM600.
•
GOOSERCV_BIN instances 0 and 1 are used for blocking protection functions.
Signals from these two GOOSERCV_BINs are connected to ISWGAPC9.
ISWGAPC9 is used to configure which protection function block is blocked.
•
GOOSERCV_BIN instances 2 and 3 are used for tripping from GOOSE. Signals
from these two GOOSERCV_BINs are connected to TRPPTRC1 and
TRPPTRC2 trip.
•
GOOSERCV_BIN instances 4 to 19 are used for blocking the circuit breaker
operation. Signals from these 16 GOOSERCV_BINs are connected to
ISWGAPC10. ISWGAPC10 is used to configure the GOOSE input signal to
block the circuit breaker open or close operation.
Section 3
1MRS757455 E
REB611 standardized configuration
54
REB611
Application Manual