background image

Relion

®

 611 series

Busbar and Multipurpose Differential

Protection and Control

REB611

Product Guide

Summary of Contents for Relion 611 series REB611

Page 1: ...Relion 611 series Busbar and Multipurpose Differential Protection and Control REB611 Product Guide ...

Page 2: ...cessories and ordering data 29 22 Tools 30 23 Terminal diagram 32 24 References 32 25 Functions codes and symbols 33 26 Document revision history 34 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB ABB assumes no responsibility for any errors that may appear in this document Copyright 2012 ABB All rights reserved Tra...

Page 3: ...have been entered the installed IED is ready to be put into service The further addition of communication functionality and interoperability between substation automation devices offered by the IEC 61850 standard adds flexibility and value to end users as well as electrical system manufacturers 2 Standard configuration REB611 is available in one standard configuration To increase the user friendli...

Page 4: ... circuit supervision instance 2 CT supervision for high impedance protection scheme instance 1 CT supervision for high impedance protection scheme instance 2 CT supervision for high impedance protection scheme instance 3 Measurement Disturbance recorder Three phase current measurement instance 1 3 Residual current measurement instance 1 Included 1 The instances of a protection function represent t...

Page 5: ...REB611 can be used in the protection of a motor or generator using the combined restricted earth fault and residual earth fault protection functionalities Due to the individuality of the high impedance protection functions a single REB611 can be used for restricted earth fault protection of both the high and low voltage side of a power transformer The high impedance principle for busbar differenti...

Page 6: ...used as bus wire supervision especially in new or retrofitting applications where an earth fault protection function is used for grounding the measurement circuits where short circuiting or circuit breaks have occurred The grounding can be done by an external relay Zone B 3 3 3 Incoming Outgoing Feeder for Zone A REB611 REB611 Incoming Outgoing Feeder for Zone B 3 3 3 Zone A Bus coupler GUID 9D830...

Page 7: ...REB611 STANDARD CONF A 3 1 3 3 Lockout relay 86 G Hi 87 Hi 87 MCS 1I MCS 1I 3I BF 51BF Io BF 51N BF Io 50N Io 51N 1 1 1 G Lockout relay 86 Hi 87 Hi 87 Hi 87 MCS 1I MCS 1I 3I BF 51BF Io BF 51N BF Io 50N Io 51N 1 GUID 55BADD92 9638 443A 9EB2 026DEA615AC3 V1 EN Figure 4 Protection of two generators one with restricted earth fault and the other with high impedance differential both combined with stand...

Page 8: ...l display of the Web browser based HMI of COM600 presents a single line diagram feature that is especially useful for the 611 series IEDs because of the limited size of the LHMI Further the WHMI of COM600 offers an overview of the whole substation including IED specific single line diagrams thus enabling convenient information accessibility To enhance personnel safety the WHMI also enables remote ...

Page 9: ...eaker or contactor with dedicated push buttons for opening and closing Control is achieved via the IED s LHMI or a remote system for example the Protection and Control IED Manager COM600 By default the IED is equipped with a single input interlocking scheme For the creation of additional interlocking schemes secured object control SOC blocking based protection schemes or external tripping binary G...

Page 10: ...ion can further be accessed either locally or remotely using the Web browser based user interface 10 Recorded data The IED has the capacity to store the records of the 32 latest fault events The records enable the user to analyze the most recent power system events Each record includes current residual voltage and angle values start times of the protection blocks time stamp and so on The fault rec...

Page 11: ... IEDs is only enabled by the IEC 61850 communication protocol The IEC 61850 communication implementation supports monitoring and control functionality Additionally parameter settings and disturbance and fault records can be accessed using the IEC 61850 protocol Disturbance records are available to any Ethernet based application in the standard COMTRADE file format The IED supports simultaneous eve...

Page 12: ...us protocol Managed Ethernet switch with RSTP support Managed Ethernet switch with RSTP support Network Network REF611 Overcurrent Earth fault Phase unbalance Thermal overload AR sequence in progress Disturb rec trigged Trip circuit failure Breaker failure REF611 Overcurrent Earth fault Phase unbalance Thermal overload AR sequence in progress Disturb rec trigged Trip circuit failure Breaker failur...

Page 13: ...2 V DC 24 V DC 80 Burden of auxiliary voltage supply under quiescent Pq operating condition DC 12 0 W nominal 18 0 W max AC 16 0 W nominal 21 0 W max DC 12 0 W nominal 18 0 W max Ripple in the DC auxiliary voltage Maximum 15 of the DC value at frequency of 100 Hz Fuse type T4A 250 V Table 8 Energizing inputs Description Value Rated frequency 50 60 Hz Current inputs Rated current In 0 2 1 A1 1 5 A2...

Page 14: ...5 s 30 A Breaking capacity when the control circuit time constant L R 40 ms 1 A 0 25 A 0 15 A Minimum contact load 100 mA at 24 V AC DC 2 4 VA Table 11 Signal outputs and IRF output Description Value Rated voltage 250 V AC DC Continuous contact carry 5 A Make and carry for 3 0 s 10 A Make and carry 0 5 s 15 A Breaking capacity when the control circuit time constant L R 40 ms at 48 110 220 V DC 1 A...

Page 15: ...0 V AC DC Continuous contact carry 5 A Make and carry for 3 0 s 15 A Make and carry for 0 5 s 30 A Breaking capacity when the control circuit time constant L R 40 ms at 48 110 220 V DC 1 A 0 25 A 0 15 A Minimum contact load 100 mA at 24 V AC DC 2 4 VA Table 14 Front port Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate Front TCP IP protocol Standard Ethernet CAT 5 cable wit...

Page 16: ...6 106 kPa Altitude Up to 2000 m Transport and storage temperature range 40 85ºC 1 Degradation in MTBF and HMI performance outside the temperature range of 25 55ºC 2 For IEDs with an LC communication interface the maximum operating temperature is 70ºC Table 19 Environmental tests Description Type test value Reference Dry heat test humidity 50 96 h at 55ºC 16 h at 85ºC IEC 60068 2 2 Cold test 96 h a...

Page 17: ...0255 22 3 class III 10 V m f 900 MHz ENV 50204 IEC 60255 22 3 class III 20 V m rms f 80 1000 MHz IEEE C37 90 2 2004 Fast transient disturbance tests IEC 61000 4 4 IEC 60255 22 4 IEEE C37 90 1 2002 All ports 4 kV Surge immunity test IEC 61000 4 5 IEC 60255 22 5 Communication 2 kV line to earth Other ports 4 kV line to earth 2 kV line to line Power frequency 50 Hz magnetic field IEC 61000 4 8 Contin...

Page 18: ...0 m distance 230 1000 MHz 47 dB µV m quasi peak measured at 10 m distance Table 21 Insulation tests Description Type test value Reference Dielectric tests IEC 60255 5 and IEC 60255 27 Test voltage 2 kV 50 Hz 1 min 500 V 50 Hz 1 min communication Impulse voltage test IEC 60255 5 and IEC 60255 27 Test voltage 5 kV 1 2 50 μs 0 5 J 1 kV 1 2 50 μs 0 5 J communication Insulation resistance measurements ...

Page 19: ...ic test IEC 60255 21 3 Class 2 Table 23 Product safety Description Reference LV directive 2006 95 EC Standard EN 60255 27 2005 EN 60255 1 2009 Table 24 EMC compliance Description Reference EMC directive 2004 108 EC Standard EN 50263 2000 EN 60255 26 2007 Table 25 RoHS compliance Description Complies with RoHS directive 2002 95 EC Busbar and Multipurpose Differential Protection and Control 1MRS7574...

Page 20: ...of the set value or 20 ms 1 Measurement mode default depends on stage current before fault 0 0 x In fn 50 Hz fault current with nominal frequency injected from random phase angle results based on statistical distribution of 1000 measurements 2 Includes the delay of the signal output contact Table 27 High impedance differential protection HIPDIF main settings Parameter Values Range Unit Step Defaul...

Page 21: ...tio Typical 0 96 Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 4 Suppression of harmonics RMS No suppression DFT 50 dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression 1 Function not included 2 Measurement mode default depends on stage current before fault 0 0 ...

Page 22: ... Technical data chapter Table 30 Circuit breaker failure protection CCBRBRF Characteristic Value Operation accuracy Depending on the frequency of the current measured fn 2 Hz 1 5 of the set value or 0 002 x In Operate time accuracy 1 0 of the set value or 20 ms Table 31 Circuit breaker failure protection CCBRBRF main settings Parameter Function Value Range Step Current value Operating phase curren...

Page 23: ... IEC Very inv 11 IEC inv 12 IEC Ext inv 13 IEC S T inv 14 IEC L T inv 15 IEC Def Time 17 Programmable 18 RI type 19 RD type Operating curve type voltage protection 5 ANSI Def Time 15 IEC Def Time 17 Inv Curve A 18 Inv Curve B 19 Inv Curve C 20 Programmable 21 Inv Curve A 22 Inv Curve B 23 Programmable Busbar and Multipurpose Differential Protection and Control 1MRS757467 B REB611 Product version 1...

Page 24: ... DFT 50 dB at f n x fn where n 2 3 4 5 RMS No suppression Table 34 Residual current measurement RESCMMXU Characteristic Value Operation accuracy Depending on the frequency of the current measured f fn 2 Hz 0 5 or 0 002 x In at currents in the range of 0 01 4 00 x In Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 RMS No suppression Busbar and Multipurpose Differential Protection and...

Page 25: ...inite time mode 1 0 of the set value or 20 ms Table 36 CT supervision for high impedance protection scheme HZCCRDIF main settings Parameter Values Range Unit Step Default Description Start value 1 0 100 0 In 0 1 10 0 Start value percentage of the nominal current Alarm delay time 100 300000 ms 10 3000 Alarm delay time Alarm output mode 1 Non latched 3 Lockout 3 Lockout Select the operation mode for...

Page 26: ...e local mode during maintenance work and that the circuit breakers cannot be operated remotely from the network control center GUID 8DC31119 E1C4 42DA 848B 968FBF8F8F53 V1 EN Figure 7 Front panel of 611 series IEDs 18 Mounting methods Using appropriate mounting accessories the standard IED case for the 611 series IED can be flush mounted semi flush mounted or wall mounted The flush mounted and wal...

Page 27: ...IED casings of the current measuring IEDs are equipped with automatic operating contacts that short circuit the current transformer secondary circuits when the IED unit is withdrawn from its case The IED casing is also equipped with a mechanical coding system that prevents current measuring IED units from being inserted into voltage measuring IED casings and vice versa that is the IED casings are ...

Page 28: ...ED series 611 series IED 611 7 IED casing and test switches Complete relay H Complete relay with test switch installed and wired in 19 cover plate K Complete relay with test switch installed and wired for Combiflex rack mounting L 8 Standard IEC B CN C GUID 3CD1BE4B 5A40 4687 9C87 FA8150C2B732 V R E B 6 1 1 H B A A A A 1 N N 1 X E Description 9 Standard configuration High impedance differential A ...

Page 29: ...ned semi flush mounting kit 1MRS050831 19 rack mounting kit with cut out for one IED 1MRS050694 19 rack mounting kit with cut out for two IEDs 1MRS050695 Mounting bracket for one IED with test switch RTXP in 4U Combiflex RHGT 19 variant C 2RCA022642P0001 Mounting bracket for one IED in 4U Combiflex RHGT 19 variant C 2RCA022643P0001 19 rack mounting kit for one IED and one RTXP18 test switch the te...

Page 30: ... front panel user interface LHMI The functionality of the interface can be limited to read only access by means of PCM600 The IED connectivity package is a collection of software and specific IED information which enable system products and tools to connect and interact with the IED The connectivity packages reduce the risk of errors in system integration minimizing device configuration and set up...

Page 31: ...agement IED signal configuration signal matrix Modbus communication configuration communication management Saving of IED parameter settings in the tool Disturbance record analysis IEC 61850 communication configuration GOOSE communication configuration Phasor diagram viewing Event viewing Saving of event data on the user s PC Supported Busbar and Multipurpose Differential Protection and Control 1MR...

Page 32: ...bstationautomation portal offers you information about the distribution automation product and service range You will find the latest relevant information on the REB611 protection IED on the product page The download area on the right hand side of the Web page contains the latest product documentation such as technical reference manual installation manual operators manual and so on The selection t...

Page 33: ...GAPC Output switch group 2 OSWGAPC OSWGAPC OSWGAPC Selector switch group 3 SELGAPC SELGAPC SELGAPC Control Circuit breaker control CBXCBR1 I O CB I O CB Supervision Trip circuit supervision instance 1 TCSSCBR1 TCS 1 TCM 1 Trip circuit supervision instance 2 TCSSCBR2 TCS 2 TCM 2 CT supervision for high impedance protection scheme instance 1 HZCCRDIF1 MCS 1I 1 MCS 1I 1 CT supervision for high impeda...

Page 34: ...ry Document revision date Product series version History A 2011 11 18 1 0 First release B 2012 05 04 1 0 Content updated Busbar and Multipurpose Differential Protection and Control 1MRS757467 B REB611 Product version 1 0 34 ABB ...

Page 35: ...35 ...

Page 36: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS757467 B Copyright 2012 ABB All rights reserved ...