Figure 195:
A simple radial power system
en06000586.vsd
0
200
400
600
800
1000
1200
1400
1600
1800
100
200
300
400
500
P[MW]
U
[k
V
]
U
limit
P
0
P
3
0
P
5
0
P
7
0
IEC06000586 V1 EN-US
Figure 196:
Voltage profile for a simple radial power line with 0, 30, 50 and
70% of compensation
8.13.3.2
Increase in power transfer
GUID-C9163D4E-CC2B-4645-B2AC-2C8A3FE3D337 v3
The increase in power transfer capability as a function of the degree of
compensation for a transmission line can be explained by studying the circuit
shown in figure
. The power transfer on the transmission line is given by the
:
( )
( )
(
)
sin
sin
1
d
d
×
×
×
×
=
=
-
× -
A
B
A
B
Line
C
Line
C
U
U
U
U
P
X
X
X
K
EQUATION1897 V1 EN-US
(Equation 360)
The compensation degree K
c
A
B
-jX
C
P
A
Q
A
P
B
Q
B
U
A
U
B
U
+jX
L
U
A
U
B
d
D
en06000590.vsd
IEC06000590 V1 EN-US
Figure 197:
Transmission line with series capacitor
The effect on the power transfer when considering a constant angle difference (δ)
between the line ends is illustrated in figure
. Practical compensation degree
runs from 20 to 70 percent. Transmission capability increases of more than two
times can be obtained in practice.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
375
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...