Z
load
U
min
3 I
max
×
----------------------
=
EQUATION574 V1 EN-US
(Equation 224)
Z
loadmin
U
2
S
-------
=
EQUATION571 V1 EN-US
(Equation 225)
Where:
U
is the minimum phase-to-phase voltage in kV
S
is the maximum apparent power in MVA.
The load angle
ArgLd
can be derived according to equation
:
max
cos
max
P
ArgLd
a
S
=
æ
ö
ç
÷
è
ø
EQUATION1623 V1 EN-US
(Equation 226)
where:
Pmax
is the maximal active power transfer during emergency conditions and
Smax
is the maximal apparent power transfer during emergency conditions.
The
RLd
can be calculated according to equation
:
cos(
)
RLd
ZLoad
ArgLd
=
×
EQUATION1624 V1 EN-US
(Equation 227)
The setting of
RLd
and
ArgLd
is by default set to 80 ohm/phase and 20 degrees.
Those values must be adapted to the specific application.
8.9
Distance protection zone, quadrilateral
characteristic, separate settings ZMRPDIS,
ZMRAPDIS and ZDRDIR
GUID-7308DB86-32CE-4615-95DC-92BEEF69E184 v1
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
289
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...