![ABB REL670 2.2 IEC Applications Manual Download Page 294](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789294.webp)
IMaxLoad
=1.2 ILoad
EQUATION1614 V2 EN-US
(Equation 222)
where:
1.2
is the security margin against the load current and
ILoad
is the maximal load current during emergency conditions.
The current ILoad can be defined according to equation
.
max
3
S
ILoad
ULmn
=
×
EQUATION1615 V1 EN-US
(Equation 223)
where:
Smax
is the maximal apparent power transfer during emergency conditions and
ULmn is the phase-to-phase voltage during the emergency conditions at the IED location.
8.8.3.1
Load encroachment
SEMOD154782-39 v4
The load encroachment function has two setting parameters,
RLd
for the load
resistance and
ArgLd
for the inclination of the load sector (see figure
).
R
X
RLdFw
RLdRv
ARGLd
ARGLd
ARGLd
ARGLd
en05000226.vsd
IEC05000226 V1 EN-US
Figure 145:
Load encroachment characteristic
The calculation of the apparent load impedance Z
load
and minimum load
impedance Z
loadmin
can be done according to equations:
Section 8
1MRK 506 369-UEN B
Impedance protection
288
Line distance protection REL670 2.2 IEC
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...