![ABB REL670 2.2 IEC Applications Manual Download Page 171](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789171.webp)
Capacitive
Inductive
200
400
600
800
1000
200
400
600
Q
(Mvar)
500
1000
1500
Power flow
(MW)
(T.L.)
(S.C.)
(T.L. + S.C.)
Transmission
Line
Series
Compensation
500 kV
500 km
k = 50 %
en06000589.vsd
IEC06000589 V1 EN-US
Figure 70:
Self-regulating effect of reactive power balance
Increase in power transfer
SEMOD168320-45 v2
The increase in power transfer capability as a function of the degree of
compensation for a transmission line can be explained by studying the circuit
shown in figure
. The power transfer on the transmission line is given by the
( )
( )
(
)
sin
sin
1
d
d
×
×
×
×
=
=
-
× -
A
B
A
B
Line
C
Line
C
U
U
U
U
P
X
X
X
K
EQUATION1897 V1 EN-US
(Equation 47)
The compensation degree K
c
A
B
-jX
C
P
A
Q
A
P
B
Q
B
U
A
U
B
U
+jX
L
U
A
U
B
d
D
en06000590.vsd
IEC06000590 V1 EN-US
Figure 71:
Transmission line with series capacitor
The effect on the power transfer when considering a constant angle difference (δ)
between the line ends is illustrated in figure
. Practical compensation degree runs
from 20 to 70 percent. Transmission capability increases of more than two times
can be obtained in practice.
1MRK 506 369-UEN B
Section 8
Impedance protection
Line distance protection REL670 2.2 IEC
165
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...