![ABB REL670 2.2 IEC Applications Manual Download Page 117](http://html.mh-extra.com/html/abb/rel670-2-2-iec/rel670-2-2-iec_applications-manual_4789117.webp)
IEC140000119-2-en.vsd
IEC140000119 V2 EN-US
Figure 34:
Multiple instances of PHASORREPORT blocks
Figure
shows both instances of ANALOGREPORT function blocks. The
instance number is visible in the bottom of each function block. For each instance,
there are three separate ANALOGREPORT blocks capable of reporting up to 24
Analog signals (8 Analog signals in each ANALOGREPORT block). These can
include for example transfer of active and reactive power or reporting the
milliampere input signals to the PDC clients as defined in IEEE C37.118 data
frame format.
IEC140000120-2-en.vsd
IEC140000120 V2 EN-US
Figure 35:
Multiple instances of ANALOGREPORT blocks
Figure
shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate BINARYREPORT blocks capable of reporting up to 24 Binary
signals (8 Binary signals in each BINARYREPORT block). These binary signals
can be for example dis-connector or breaker position indications or internal/
external protection alarm signals.
1MRK 506 369-UEN B
Section 6
Wide area measurement system
Line distance protection REL670 2.2 IEC
111
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...