Section 6
Wide area measurement system
6.1
C37.118 Phasor Measurement Data Streaming
Protocol Configuration PMUCONF
GUID-747C6AD7-E6A1-466E-92D1-68865681F92F v1
6.1.1
Identification
GUID-1E140EA0-D198-443A-B445-47CEFD2E6134 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Configuration parameters for IEEE
1344 and C37.118 protocol
PMUCONF
-
-
6.1.2
Application
GUID-33694C62-A109-4D8F-9063-CEFA5D0E78BC v4
The IED supports the following IEEE synchrophasor standards:
•
IEEE 1344-1995 (Both measurements and data communication)
•
IEEE Std C37.118-2005 (Both measurements and data communication)
•
IEEE Std C37.118.1–2011 and C37.118.1a-2014 (Measurements)
•
IEEE Std C37.118.2-2011 (Data communication)
PMUCONF contains the PMU configuration parameters for both IEEE C37.118
and IEEE 1344 protocols. This means all the required settings and parameters in
order to establish and define a number of TCP and/or UDP connections with one or
more PDC clients (synchrophasor client). This includes port numbers, TCP/UDP IP
addresses, and specific settings for IEEE C37.118 as well as IEEE 1344 protocols.
6.1.3
Operation principle
GUID-2608FBC4-9036-476A-942B-13452019BC11 v2
demonstrates the communication configuration diagram. As can be
seen, the IED can support communication with maximum 8 TCP clients and 6 UDP
client groups, simultaneously. Every client can communicate with only one
instance of the two available PMUREPORT function block instances at a time. It
means that one client cannot communicate with both PMUREPORT:1 and
PMUREPORT:2 at the same time. However, multiple clients can communicate
with the same instance of PMUREPORT function block at the same time. For TCP
clients, each client can decide to communicate with an existing instance of
PMUREPORT by knowing the corresponding PMU ID for that PMUREPORT
instance. Whereas, for UDP clients, the PMUREPORT instance for each UDP
channel is defined by the user in the PMU and the client has to know the PMU ID
corresponding to that instance in order to be able to communicate. More
1MRK 506 369-UEN B
Section 6
Wide area measurement system
Line distance protection REL670 2.2 IEC
105
Application manual
Summary of Contents for REL670 2.2 IEC
Page 1: ...RELION 670 SERIES Line distance protection REL670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 32: ...26 ...
Page 70: ...64 ...
Page 110: ...104 ...
Page 152: ...146 ...
Page 564: ...558 ...
Page 570: ...564 ...
Page 592: ...586 ...
Page 706: ...700 ...
Page 804: ...798 ...
Page 848: ...842 ...
Page 860: ...854 ...
Page 882: ...876 ...
Page 896: ...890 ...
Page 906: ...900 ...
Page 907: ...901 ...