The residual overcurrent protection in line end A is considered. See figure
principle can be used for the other line end.
3.1.10.1
Calculating general settings
1.
Set
GlobalBaseSel
to
1
The settings are made in primary values. These values are given in the base settings
in Global base 1 (= 1000 A for this example).
2.
Set
DirModeSel1
and
DirModeSel2
to
Forward
The function shall be set directional forward for steps 1 and 2.
3.
Set
DirModeSel4
to
Non-directional
.
3.1.10.2
Calculating settings for step 1
1.
Set
Pickup1
to
300 %
of
IBase
Busbar faults at the remote line end are applied, see figure
. The following fault
types are applied: phase-phase-ground short circuit and phase-ground-fault. For the
faults shown in the figure, the source impedance (both positive sequence and zero
sequence) at line end A should be minimized (maximum short circuit power).
Z 1 = R 1 + jX 1
Z 0 = R 0 + jX0
A
B
Step 1- reach
C
Communication
Step 2- reach
Step 1- reach
Step 2- reach
Y
Y
REL 650
REL 650
ANSI11000177_1_en.vsd
ANSI11000177 V1 EN
Figure 23:
Fault case for step 1 calculation
The calculations provide the largest residual current to the protection 3I
0max
= 2.39
kA.
To assure selectivity the setting must fulfil:
I
high,set
= 1.2 · k · 3
I0max
Section 3
1MRK 506 334-UUS A
REL650 setting examples
72
Application manual
Summary of Contents for REL650 series
Page 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Page 2: ......
Page 30: ...24...
Page 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Page 110: ...104...
Page 260: ...254...
Page 274: ...268...
Page 280: ...274...
Page 396: ...390...
Page 494: ...488...
Page 506: ...500...
Page 515: ...509...