1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
53
*)
Note that the value of SGB1/3 has to be 0 (indications, output contacts and memorized values will not
be reset by the binary input signal).
Control parameters
Table 4.1.9.4-5
Disturbance recorder internal triggering
Event
Weighting
factor
Default value of
triggering mask,
V241
Default value of
triggering edge,
V242
Start of stage U
0b
>
1
0
0
Trip of stage U
0b
>
2
0
0
Start of stage I
0
> or U
0
>
4
0
0
Trip of stage I
0
> or U
0
>
8
1
0
Start of stage I
0
>> or U
0
>>
16
0
0
Trip of stage I
0
>> or U
0
>>
32
0
0
Not in use
-
0
0
Not in use
-
0
0
Checksum
8
0
Table 4.1.9.4-6
Disturbance recorder external triggering
Event
Weighting
factor
Default value of
triggering mask,
V243
Default value of
triggering edge,
V244
External BI
*)
1
1
0
Not in use
-
0
0
Not in use
-
0
0
Not in use
-
0
0
Not in use
-
0
0
Not in use
-
0
0
Not in use
-
0
0
Not in use
-
0
0
Checksum
1
0
Table 4.1.9.4-7
Control parameters
Description
Parameter
R, W
Value
Unlatching output contacts
V101
W
1 = unlatch
Clearing registers and unlatching
output contacts
V102
W
1 = clear and unlatch
Rated frequency
V133
R,W (P)
50=50 Hz
60=60 Hz
Nominal voltage
V134
R,W (P)
100, 110, 115, 120 (V)
Remote control of settings
V150
R,W
0 = setting group 1
1 = setting group 2
Non-volatile memory settings
V152
R, W
0...31
Event mask for I
0
>, U
0
> and U
0b
>
V155
R,W
0...255, see Event codes
Event mask for I
0
>> and U
0
>>
V156
R,W
0...15, see Event codes
Event mask for output contacts’
events
V157
R,W
0...255, see Event codes