52
1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
Disturbance recorder
1)
M1 can be used for broadcast triggering by using the unit address “900”.
2)
Parameters can be written when the recorder has not been triggered.
3) The disturbance recorder requires this parameter to be set. The conversion factor is the transforma-
tion ratio multiplied by the rated current of the relay. If this parameter has been given the default value
0, dashes will be shown on the LCD instead of the primary values and the recorded data will be redun-
dant.
Table 4.1.9.4-4
Parameters for the disturbance recorder
Description
Parameter
R, W
Value/Note
Manual triggering
M1
1)
W
1
Clear recorder memory
M2
W
1
Sampling rate
M15
2)
R, W
800/960 Hz
400/480 Hz
50/60 Hz
Station identification/unit number
M18
R, W
0…9999
Rated frequency
M19
R
50 or 60 Hz
Station name
M20
R, W
Max 16 characters
Digital channel texts
M40...46
R
Analogue channel texts
M60...61
R
Analogue channel: rated voltage
and unit of primary voltage
transformer
M80
3)
R, W
Factor 0.00...600, unit (V, kV),
e.g. 20.0,kV)
Analogue channel: conversion
factor and unit, I
0
M81
3)
R, W
Factor 0...65535, unit (A, kA),
e.g. 10.0,kA
Post-triggering recording length
V240
R, W
0...100%
Internal trigger signals’ checksum V241
R,W
0...63, see table 4.1.9.4-5
Internal trigger signal’s edge
V242
R,W
0...63; 0 = rising, 1 = falling
External trigger signal (BI)
V243
R,W
0/1, see table 4.1.9.4-6
External trigger signal’s edge
V244
R,W
0/1; 0 = rising, 1 = falling
Triggering state, clearing and
restart
V246
R,W
R:
0 = recorder not triggered
1 = recorder triggered and
recording stored in the
memory
W:
0 = clear recorder memory
2 = download restart; sets the
first information and the time
stamp for triggering ready to
be read
4 = manual triggering