1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
17
)LJ 2SHUDWLRQFKDUDFWHULVWLFVLQ
ϕ
)LJ 2SHUDWLRQFKDUDFWHULVWLFFRV
ϕ
The operation directions, forward or reverse, of the directional earth-fault stages can
be selected independently of each other. The directional stages can also be
separately configured to be non-directional.
When the earth-fault current exceeds the set start value of low-set stage I
0
>, the
earth-fault unit will start to deliver a start signal after a ~ 70 ms’ start time. When
the set operate time at definite-time characteristic or the calculated operate time at
IDMT characteristic elapses, the earth-fault unit will deliver a trip signal.
ϕ
Io
Uo
Io>(>)
ϕ
c=2..7°
ϕ
c=2..7°
Sin_fi_char
ϕ
Io
Uo
Io>(>)
ϕ
c=2..7°
ϕ
c=2..7°
Cos_fi_char