1MRS 751055-MUM
Directional or Non-Directional Earth-Fault Relay
Operator’s Manual
REJ 527
• CONFIGURATION
3.2.4.2.
How to change settings
Actual settings are found in the first submenu, and they are not editable. Actual
settings consist of settings either of group 1 or 2, depending on which of these are
selected to be active. Settings of group 1 and 2 can be edited in the setting mode; see
the instructions later in this section.
)LJ 6HWWLQJV
Both the setting groups have their related registers. Switching between the setting
groups 1 and 2 enables changing a whole group of settings at the same time. You can
switch between the setting groups 1 and 2 in three different ways:
1. by selecting “Group 1/Group 2” under the main menu group “Settings”
2. with a binary input signal BI
3. with the command V150 via serial communication bus.
)LJ 6HWWLQJJURXSVHWWLQJJURXS
When a large number of setting values is to be altered, e.g. during commissioning of
relay systems, it is recommended that you use a personal computer provided with
the necessary software. When these are not available or when only a few settings are
to be altered, proceed as follows:
1. Select the main menu group “Settings”, and further the “Protect.stages”. Press
the [
→
] button to enter the actual settings.
2. Use the arrow button [
↓
] to select the setting to be changed and press the [
→
]
button.
3. Enter the setting mode by pressing the [E] button. If the default password has
been changed, the text PASSWORD appears on the display and you have to give
Io>
: x.xx%
Uo>
: x.xx%
to>
: x.xxs
k>
: x.xx
Io>>
: x.xx%
Sett527
Uo>>
: x.xx%
to>>
: x.xxs
Uob>
: x.xx%
tb>
: x.xxs
E
C
Main Menu
Group Menu
Parameter Menu
MEASUREMENTS
RECORDED DATA
SETTINGS
CONFIGURATION
INFO
CBFP
SETTINGS
PROTECT. STAGES
SGF
SGB
SGR
GRPOUP 1 /GROUP 2
SETTINGS
NEW TRIP IND.
Edit/Confirm
Cancel
GRP2
Io>
: x.xx
SETTINGS
*GRP1
Io>
: x.xx
ϕ
a
:x
°
ϕ
b
:-x
°
ϕ
c
:x
°
Io>
: x.
xx%
GrS527
SETTINGS
SETTINGS
*GRP 1
Io>
: x.xx
Cancel
Confirm
GRP 2
Io>
: x.xx
Submenu
Parameter Menu
C
E