Indicated result
Possible reason
Proposed action
ADC-module OK
No problem detected.
None.
ADC-module Fail
The AD conversion
module has failed.
Contact your ABB representative for service.
(Protocol name) Ready
No problem detected.
None.
(Protocol name) Fail
Protocol has failed.
(I/O module name)
Ready
No problem detected.
None.
(I/O module name) Fail
I/O modules has failed.
Check that the I/O module has been
configured and connected to the IOP1- block.
If the problem persists, contact your ABB
representative for service.
15.2
Fault tracing
15.2.1
Internal fault indications
If an internal fault has occurred, the local HMI displays information under
Main
menu/Diagnostics/IED status/General
Under the Diagnostics menus, indications of a possible internal failure (serious fault)
or internal warning (minor problem) are listed.
Indications regarding the faulty unit are outlined in table
Table 19:
Self-supervision signals on the local HMI
HMI Signal Name:
Status
Description
INT Fail
OFF / ON
This signal will be active if one or more of
the following internal signals are active;
INT--LMDERROR, INT--WATCHDOG,
INT--APPERROR, INT--RTEERROR, or
any of the HW dependent signals
INT Warning
OFF / ON
This signal will be active if one or more of
the following internal signals are active;
INT--RTCERROR, INT--
IEC61850ERROR, INT--
TIMESYNCHERROR
ADMnn
READY / FAIL
Analog input module n failed. Signal
activation will reset the IED
BIMnn
READY / FAIL
BIM error. Binary input module Error
status. Signal activation will reset the IED
BOMn
READY / FAIL
BOM error. Binary output module Error
status.
IOMn
READY / FAIL
IOM-error. Input/Output Module Error
status.
MIMn
READY / FAIL
mA input module MIM1 failed. Signal
activation will reset the IED
RTC
READY / FAIL
This signal will be active when there is a
hardware error with the real time clock.
Table continues on next page
Section 15
1MRK502053-UEN B
Troubleshooting
248
Generator protection REG670 2.0 IEC
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...